Transient Earth Voltage PD Detector

Transient Earth Voltage PD Detector

Our transient earth voltage PD detectors can detect the switchgear, transformer and other power equipment's TEV signal when these devices occur partial discharge , in order to determine the equipment of the PD status and nature.

Core standards

  • IEC 62478/TS/Ed1 High voltage test techniques-Measurement of partial discharges by electromagnetic and acoustic methods 
  • DL/T 417-2006 Guide for partial discharge measuring of power equipment
  • Q/GDW 11063-2013 Technical specification for transient earth voltage partial discharge detector
  • Q/GDW 11060-2013 Field application guide for transient earth voltage partial discharge on-site testing technology of alternating-current metal-enclosed switchgear

Various types of sensors

Switchgear's TEV PD detector

TEV sensors are used for field testing

Features

  • Principle
     Using capacitance coupled technology to collect the partial discharge signals and test TEV of switchgear to analyze the safety of switchgear.
  • Anti-interference
    Using our signal identification technology and according to the strength characteristics, the background signals will be erased. According to the phase characteristics, the signals in any phase point and band can be erased. You can choose any phase point and band to test.
  • Analysis and diagnosis
    The instrument has more methods like one single circle, peak value and PRPD to get the peak values, effective values, phases, times of partial discharges and full circle or half circle amplitude etc.  The test data is shown in circle chart, statistic chart, trend chart, frequency chart and PRPD chart etc. The instrument has some useful setting functions. We supply some typical charts. Some are  from our long time experience of after sales  service and some are from well-known charts to help the tester to analyze the possible defects in equipments. Using outside synchronization unit the phase can be locked.
    Using more sensors the partial discharges can be located. 
  • Calibration
    Using the standard signals generator calibration can be done in our instruments.

Technical Parameters

  • Precision:                            ≤10pC.
  • Testing frequency band:     3~100MHz.
  • Signal sampling:                 Sampling accuracy 16Bit,Sampling rate:250MS/s.
  • Dynamic Range:                 60dB.
  • Synchronization mode:       wired, wireless;frequency 30~300Hz;voltage AC10~380V;Wireless distance 75m. 
  • Stability:                              ±5%.
  • Linearity error:                    ±3%.
  • Battery:                                lithium battery,24V/5Ah.
  • Dimension:                          236×177×53mm.
  • Weight:                                1.5kg.

Product model

Model

Name

Passage

Description

XD55xx

TEV PD detector

1~4

switchgear

XD5552

TEV and acoustic PD combined detector

2~4

switchgear

XD50xx

Portable PD detector

2~4

quick check

Switchgear PD positioning

Use the headphones to listen when the switchgear occurs PD

Test report

    Product Category