Core standards
- GB/T 7354-2003 Partial discharge measurtments (IEC60270:2000 IDT)
- Q/GDW 11063-2013 Technical specification for ultrasonic partial discharge detector
- Q/GDW 11304.5-2015 Technical specification for energized test device of electrical equipment Part5:Technical specification for high-frequency partial discharge detector
Various types of sensors |
Detection unit |
Transformers electro acoustic positioning |
Features
- High accuracy
The instrument uses pulse current, ultrasonic, high frequency, ultra high frequency and other detection means to verify the results of the PD test, the PD detection accuracy is very high.
- High sensitivity
The detection sensitivity is less than 0.1pC.
- Precise positioning
The instrument uses three-dimensional modeling positioning technology, can accurately locate the PD position.
- Strong anti - jamming technology
The instrument's design is the use of spectrum analysis, frequency filtering, signal separation and other technical means, can effectively filter out the interference signal. - Strong diagnostic and analysis capabilities
There is a big data base in our system. It has the typical curves for different kinds of defects. The history records are saved in system. It’s easy to find the potential problems per comparing with the records.
- Wireless
Every unit is wireless and working per battery. So it’s easy to install it in different positions. It saves a lot of works and costs.
- Distributed placement
The sensor and the detection unit can be arranged at each detection position of the transformer.
- Good compatibility
Support the transformer built-in sensors and third-party testing equipments access to our instruments.
- Easy installation
Detection unit, the sensor can be fixed on the transformer to the magnet, strap, buckle, etc., on-site installation is convenient.
- Wide applicability
The instrument is suitable for all kinds of high voltage test power supply.
Technical Parameters
- Precision: ≤0.1pC.
- Testing frequency band: pulse current 0~1000kHz, UHF 300~1500MHz, HF 1~30MHz, AE 10~300kHz.
- positioning accuracy: ≤10cm.
- Time base synchronization: ≤10ns.
- Synchronization mode: wired, wireless; frequency 30~300Hz; voltage AC10~380V; accuracy0.01°.
- Communication: WIFI, optical fiber, RJ45.
- Battery: lithium battery, 24V/5Ah.
Product model
Model | Name | Unit | Detection channel |
Remarks | |||
AE | UHF |
TEV | HF | ||||
XD50WT |
Transformer PD Detecting and Positioning System |
4 | 8 | 4 | / | 4 | Can be added on demand |
Transformer high frequency detection |
Transformer UHF detection |
Transformer pulse current detection |